Intrinsically Safe Control, FM Approved, SPST Isolated Contacts
Quick Specs...
- Solid State Reliability
- Up to 470K Ohm/cm Sensitivity, Field-Selectable
- Internal Surge Suppression
- Single Level or Differential Service
|
|
|
Overview / Design Principle:
Series 17 intrinsically safe controls have SPST isolated contacts and are FM Approved for use in Class I or II, Groups A through G hazardous locations. Sensitivity is field-selectable through the use of external resistors supplied with the control.
Applications:
Hazardous Atmospheres
Pumps
Waste Treatment
Alarms
Sewage
CP Industry
|
|
| Specifications |
Contact Design
|
1 N.O. & 1 N.C. Isolate Contacts
|
Contact Rating (24/120/240 VAC)
|
8 amp Resistive
|
Mode of Operation
|
Direct/Inverse, factory set
|
Sensitivity
|
0-470K ohms, field adjustable
|
Primary Voltage
|
24 VAC, 120 VAC, 240 VAC (+10%/-15%) 50/60 Hz
|
Secondary Voltage
|
13 VAC, 4 mA
|
Temperature
|
-40°F to 150°F (-40°C to 65°C)
|
Approvals
|
FM File # 1G9A1.AX
|
Connections
|
All screw type connections
|
|
|
|
| A |
4-3/8" (11.11 cm) |
| B |
2-1/8" (5.40 cm) |
| C |
3-3/8" (8.57 cm) |
| D |
3" (7.62 cm) |
| E |
7/32" (.60 cm) DIA. |
|
|
|
|
|