Gems Sensors Spacer
Message
 
Loading...
Series 16 / Series 16D 

General Purpose Control / General Purpose Control with DPDT Load Contacts 

Series 16 / Series 16D 

Quick Specs... 

  • Solid State Reliability 
  • Compact Size 
  • Spade Terminals 
  • Low-Voltage Sensor 
  • Time Delays Available 
  • LED Monitoring
  • U.L. "Motor Control"  


  Overview    Specifications    Dimensions    Related Info    
               

Overview / Design Principle: 

Engineered for general purpose single-level or differential applications, these controls have spade terminals for easy wiring and provide sensitivities up to 1 million Ohms/cm. Series 16D controls are similar to Series 16, but include DPDT load contacts to eliminate the need for slave relays. 

Applications: 

  • Single-Level Service 
  • Point Level 
  • Valve Control 
  • Low-Water Cutoff 
  • Differential Service 
  • Alarms 
  • Pump Control 

Specifications 

Contact Design 

Series 16: 1 N.O. & 1 N.C. (1 Form C)
Series 16D: 2 N.O. & 2 N.C. (2 Form C)
 

Contact Rating (120,240 VAC) 

Series 16: 10 A Resistive 1/3 hp
Series 16D: 5 A Resistive 1/10 hp
 

Mode of Operation 

Direct or Inverse, factory set 

Sensitivity 

0-1M Ohm, factory set 

Primary Voltage 

120 VAC, 240 VAC, 24 VAC, 208 VAC (+10%/-15%) 50/60 Hz 

Secondary Voltage 

12 VAC, 1.5 mA 

Temperature 

-40°F to 150°F (-40°C to 65°C)

Approvals 

U.L. 508 File # E 44426

Terminal Style 

Spade connection 

Options 

Time Delays, Retrofit Plate 

 

 Dimensions:
 DimSeries16.gif 
A  2-3/16" (5.55 cm) 
B  1-3/4" (4.45 cm) 
C  3/16" (.48 cm) REF 
D  1-1/16" (2.70 cm) REF 
E  Backplate Supplied by Others 
F  1/2" (1.27 cm) 
G  1-7/8" (4.76 cm) 
H  1" (2.54 cm) 
I  1-5/8" (4.13 cm) 
J  2-1/2" (6.35 cm) 
Wiring:
 WireSeries16.gif 
A  A.C. Supply 
B  Transformer 
C  Reference Probe 
D  For Single Level Service, Use "G" and "H" Connections 
E  High Probe 
F  Low Probe 
Additional Product Information: 
* Sockets, Standoffs & Optional Character Reference 
Overview: Conductivity-Based Liquid Level Control 
Standard & Custom Panels Overview 
Sensitivity & Material Selection Guide 
Controls Overview 
Grounding Methods for Electrode Fittings 
Product Search
Partner Sign-In